Answers to Commonly Asked Life-Safety Code Questions

A Q&A of some of building professional's most-pressing life-safety concerns

 

NFPA 25 Specifies 5-Year Fire-Sprinkler System Obstruction Inspection
Like your car, an automatic fire-sprinkler system has components that can age or wear out over time. Piping, valves, and other devices can become obstructed by foreign materials or corrode to the point where they might leak or fail under pressure. In 2002, the Quincy, MA-based National Fire Protection Association (NFPA) strengthened the inspection code requirement for automatic fire-sprinkler systems. In a move that is helping to drive proper maintenance of these critical life-safety systems, NFPA adopted a code requiring that an internal inspection of piping be conducted every 5 years or when conditions indicate the need for an internal inspection. This type of inspection can identify microbiologically influenced corrosion (MIC), rust, and slime that may obstruct the piping and compromise the system.

By Michael Lohr

In the SimplexGrinnell Fire and Life-Safety Road Show Series, the company organizes dozens of events each year where its fire- and life-safety specialists present the latest in code updates, technology advances, and best practices to industry professionals. The Q&A portion of the road show makes it quite clear that the attendees are not only curious, but also intent on doing the right thing when it comes to life safety. What follows is a compilation of the top questions asked.

Q: Can heat guns be used to test the rate of rise heat detectors?
This question can be answered by referring to NFPA 72 2007 Table 10.4.2.2 Test Methods. The answer is "yes," as long as it is not prohibited by the manufacturer of the heat detector and will not damage the non-restorable portion of the detector.

Q: Does testing smoke detectors by spraying canned smoke into a piece of conduit and holding it up to the smoke detector meet NFPA requirements?
According to NFPA 72 Chapter 10, "The detector sensitivity cannot be tested or measured using any spray device that administers an unmeasured concentration of aerosol into the detector." This would be an acceptable test for the yearly smoke entry functional test; however, the canned smoke manufacturer may not recommend or condone the use of a piece of conduit. Most canned smoke suppliers use some type of distribution nozzle to control the amount of aerosol that goes into the smoke chamber. An overabundance of aerosol in the smoke detector could cause a residue of propellant to build up. Such a residue could cause dirt to stick to the unit and thereby necessitate a cleaning. Residue could also degrade the detector's plastic and accelerate the timetable for replacement.

Q: Is sensitivity testing of each smoke detector required on an addressable system?
All smoke detectors, whether addressable or not, are required to be sensitivity tested. Under NFPA 72 Chapter 10 Table 10.4.2.2 item g, test methods that are allowed include a calibrated test method, manufacturer's calibrated sensitivity test instrument, listed control equipment arranged for the purpose, smoke detector/control unit arranged for the purpose, or other calibrated sensitivity test method approved by the Authority Having Jurisdiction (AHJ). Many of the newer addressable fire systems have the control equipment listed to automatically confirm the sensitivity of the smoke detectors. It's advisable to check with your equipment manufacturer.

Q: Do sprinkler gauges need to be replaced every 5 years?
According to NFPA 25 Chapter 5.3.2 NFPA 2002 edition, "Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced." The Water-Based Protection Systems Handbook 2002 edition provides additional guidance on this issue: "Many of the tests prescribed in NFPA 25 rely on the accuracy of pressure gauges. It is not the intent of 5.3.2 to require that each and every gauge be individually calibrated. It is acceptable to compare the reading of one gauge with that of a calibrated gauge. Other gauges on systems that are installed in similar positions and elevations (for example, on an adjacent riser) that show similar readings are acceptable."

Q: When testing fire alarm control panel batteries, do the transponders and NAC (notification appliance circuit) batteries need to be tested as well?
Yes, all transponders and interface equipment that have batteries must be tested at the same time as the control panel batteries.

Q: What are the requirements for testing roof hatches?
Assuming that the hatches are connected to the fire system for activation, NFPA 72 Chapter 10 Table 10.4.2.2 item a comes into play. "Operation of evacuation signals and auxiliary functions (outputs) is required. Test frequency would be yearly or quarterly, depending on whether the system is monitored by a supervising station."

Q: Who is responsible for flushing fire hydrants each year - the building owner, the AHJ, or the water company? Who should be notified when performing this test?
Generally, when piping enters private property, the property owner is responsible for inspection, testing, and maintenance of piping and related equipment. Piping and equipment on the public side of the property line are generally the responsibility of the water purveyor.

Q: Is it true that sprinkler heads should be replaced if they are green in color?
If there is corrosion evidence of any kind at the plug area of the sprinkler, it needs to be replaced. If there is only discoloration on the frame, replacement is not specified.

Q: How often do standpipe hoses need to be re-racked (if at all)?
In accordance with NFPA 1962, hoses need to be un-racked annually and inspected as described in 4.3.4 (in-service hose shall be un-racked, unreeled, or unrolled and physically inspected as specified in Section 4.6 at least annually; the hose shall be re-racked, re-reeled, or re-rolled so that any folds do not occur at the same position on the hose).

Q: Can an existing sprinkler head be changed out if needed on an annual inspection?
This can be done, but the work should be performed by fitters who have the training and experience to properly and safely drain and recharge the system.

Michael Lohr is director of service marketing at Boca Raton, FL-based SimplexGrinnell (www.simplexgrinnell.com). For other code questions, contact Lohr at (mikelohr@tycoint.com).

 


Visit our website today to learn about the design flexibility of a Morton building and the endless possibilities of partnering with our designBUILD team.


Wood construction is both cost and energy efficient. Check out Morton Buildings and our designBUILD team online today to discover all the benefits of post-frame construction.


When choosing a metal-clad building for your next construction project, consider Morton Buildings, Inc., and their designBUILD team, we’ll make your dream a reality.

We Can Help You Reduce Energy by 30%

Our mission is to help our customers manage their buildings' energy costs, improve reliability, and enhance performance while having a positive impact on the environment.
CLICK HERE to find out how.

 


Tennant Company is a recognized leader in designing, manufacturing and marketing solutions that help create a cleaner, safer, healthier world. With thousands of satisfied customers already using award winning ec-H2O technology, why not see what you're missing? Test ec-H2O on your soils in your facility. Get a free demo.


Tennant Company is a recognized leader in designing, manufacturing and marketing solutions that help create a cleaner, safer, healthier world. With thousands of satisfied customers already using award winning ec-H2O technology, why not see what you're missing? Test ec-H2O on your soils in your facility. Get a free demo.

 

Replace core drilling with Connectrac In-Carpet and On-Floor Wireways, the proven connectivity solution in open interior spaces of all kinds. These elegant low-profile wireways are great for AV / telecom connectivity wherever it’s needed.

 

Add highly responsive multi-zone comfort to any building project, in any climate. Our CITY MULTI H2i R2- and Y-Series VRF systems give you flexibility to fit the needs of any building. Enjoy 100% heating capacity at 0°F outdoor ambient, and 85% heating capacity at -13°F outdoor ambient.  For more information, log on to www.mitsubishipro.com


Visit our website today to learn about the design flexibility of a Morton building and the endless possibilities of partnering with our designBUILD team.


Wood construction is both cost and energy efficient. Check out Morton Buildings and our designBUILD team online today to discover all the benefits of post-frame construction.


When choosing a metal-clad building for your next construction project, consider Morton Buildings, Inc., and their designBUILD team, we’ll make your dream a reality.

We Can Help You Reduce Energy by 30%

Our mission is to help our customers manage their buildings' energy costs, improve reliability, and enhance performance while having a positive impact on the environment.
CLICK HERE to find out how.

 


Tennant Company is a recognized leader in designing, manufacturing and marketing solutions that help create a cleaner, safer, healthier world. With thousands of satisfied customers already using award winning ec-H2O technology, why not see what you're missing? Test ec-H2O on your soils in your facility. Get a free demo.


Tennant Company is a recognized leader in designing, manufacturing and marketing solutions that help create a cleaner, safer, healthier world. With thousands of satisfied customers already using award winning ec-H2O technology, why not see what you're missing? Test ec-H2O on your soils in your facility. Get a free demo.

 

Replace core drilling with Connectrac In-Carpet and On-Floor Wireways, the proven connectivity solution in open interior spaces of all kinds. These elegant low-profile wireways are great for AV / telecom connectivity wherever it’s needed.

 

Add highly responsive multi-zone comfort to any building project, in any climate. Our CITY MULTI H2i R2- and Y-Series VRF systems give you flexibility to fit the needs of any building. Enjoy 100% heating capacity at 0°F outdoor ambient, and 85% heating capacity at -13°F outdoor ambient.  For more information, log on to www.mitsubishipro.com


 
comments powered by Disqus

Related Products

Flooring
Furniture
Lighting
Vertical Transportation

Sponsored Links