Are you getting what the R-value specified and paid for?

By Darrell Smith, PE, RRC

 

The building code prescribed R-values for above deck roof insulation will be increasing again in the near future once the building code agencies adopt the 2012 ASHRAE (American Society of Heating, Refrigeration and Air-Conditioning Engineers) criteria. For Zones 4 and 5 the R-value will need to be R-25, Zone 6 – R-30 and Zones 7 and 8 up to R-35.

 


ASHRAE Climate Zone Map

 

Polyisocynaurate insulation is one of the more commonly used insulation types in the roofing industry. Most manufacturers of polyisocyanurate insulation use the long-term thermal resistance (LTTR) method of determination. LTTR method is defined by ASTM C1303, “Standard Test Method for Predicting Long-Term Thermal Resistance of Closed-Cell Foam Insulation.” The LTTR method provides for thin-slicing test specimens, which accelerates their aging process.  The specimens’ R-value is tested at a 75 degree Fahrenheit (F) laboratory condition at various defined times producing an R-value versus time relationship. The resulting LTTR is calculated as a 15-year time-weighted average of the tested values and it closely approximates the R-value after five years of aging under controlled laboratory conditions.

Although the LTTR method of R-value determination and reporting may be appropriate for laboratory analysis, research comparison and procurement purposes, NRCA (National Roofing Contractors Association) does not consider use of LTTR to be appropriate for design and in-service purposes.1 This position is consistent with NRCA’s longstanding position that the published R-values for polyisocyanurate and polyurethane foams are not consistent with actual in-service performances of these products.

When designers use polyisocyanurate insulation, NRCA recommends they determine their thermal calculations using an in-service R-value of 5.0 per inch thickness in heating conditions and 5.6 per inch thickness in cooling conditions. Designers should use the R-value for heating conditions or cooling conditions based on the predominant condition for the climate where the building being considered is located. The following table provides LTTR and NRCA recommended design R-values for commonly available thicknesses of polyisocyanurate insulation.  

 

Polyisocyanurate

Thickness,

inches                           LTTR              NRCA Recommended

                                                            Design R-values                       

                                                            Heating Conditions      Cooling Conditions

1.0                               6.0                               5.0                               5.6

1.25                             7.5                               6.3                               7.0

1.5                               9.0                               7.5                               8.4

1.75                             10.5                             8.8                               9.8

2.0                               12.1                             10.0                             11.2

2.3                               14.0                             11.5                             12.9

2.5                               15.3                             12.5                             14.0

Another factor to consider when specifying the R-value for a roofing project is the fact that installation of the insulation with a metal fastener (screw) through the entire thickness of the insulation produces a thermal bridge that reduces the effective R-value even more. A study published in 1986 shows that installation of a metal fastener with a metal cap creates and R-value reduction of 3% for 2 inch thickness

up to 8% for 6 inch thickness.2 This is based on a typical fastener density of one fastener per 2 square feet of board area for a fully adhered membrane application.

 


Figure for thermal resistance reduction

 

An example of the “true” R-value of an R-25 insulation system that may be seen in specifications for the Chicago area would be a layer of 2.3 inch and 1.75 inches of polyisocyanurate insulation.  Both layers would be mechanically fastened from the top layer into a metal deck. Using just the LTTR method this provides the code required R-value.

 

Chicago is considered a heating climate. Using the NRCA recommended R-value would only result in a value 20.3. Further reduction of the “true” R-value would include a 7% reduction per the 1986 study. This results in an actual design R-value of 18.9, far less than the code required and what the client thought they purchased.

 

Both of these factors can play into the direction the construction industry is going with the analysis of the “projected design” energy savings versus the actual energy savings of the constructed project. Designers would be prudent to take these factors into consideration for such projects as well as all projects. One way to minimize the R-value loss of fastening insulation to a metal deck would be to only fasten the bottom layer with the fastener and attach the upper layers with adhesive or bitumen. Doing this according to the 1986 study “the reduction in overall thermal resistance is about of factor of three less than that for the case in which the metal fastener penetrates the entire insulation layer”.2

 

 

 

Darrell Smith, PE, RRC is Civil Engineer - Building Envelope/Roof Consultant

REFERENCES

1.         NRCA Roofing Manual: Membrane Roof Systems-2011, National Roofing Contractors Association

2.         “Burch, Douglas M., “A Heat Transfer Analysis of Metal Fasteners in Low-Slope Roofs,” ASTM STP 959, 1986

 


Visit our website today to learn about the design flexibility of a Morton building and the endless possibilities of partnering with our designBUILD team.


Wood construction is both cost and energy efficient. Check out Morton Buildings and our designBUILD team online today to discover all the benefits of post-frame construction.


When choosing a metal-clad building for your next construction project, consider Morton Buildings, Inc., and their designBUILD team, we’ll make your dream a reality.

We Can Help You Reduce Energy by 30%

Our mission is to help our customers manage their buildings' energy costs, improve reliability, and enhance performance while having a positive impact on the environment.
CLICK HERE to find out how.

Add highly responsive multi-zone comfort to any building project, in any climate. Our CITY MULTI H2i R2- and Y-Series VRF systems give you flexibility to fit the needs of any building. Enjoy 100% heating capacity at 0°F outdoor ambient, and 85% heating capacity at -13°F outdoor ambient.  For more information, log on to www.mitsubishipro.com


Visit our website today to learn about the design flexibility of a Morton building and the endless possibilities of partnering with our designBUILD team.


Wood construction is both cost and energy efficient. Check out Morton Buildings and our designBUILD team online today to discover all the benefits of post-frame construction.


When choosing a metal-clad building for your next construction project, consider Morton Buildings, Inc., and their designBUILD team, we’ll make your dream a reality.

We Can Help You Reduce Energy by 30%

Our mission is to help our customers manage their buildings' energy costs, improve reliability, and enhance performance while having a positive impact on the environment.
CLICK HERE to find out how.

Add highly responsive multi-zone comfort to any building project, in any climate. Our CITY MULTI H2i R2- and Y-Series VRF systems give you flexibility to fit the needs of any building. Enjoy 100% heating capacity at 0°F outdoor ambient, and 85% heating capacity at -13°F outdoor ambient.  For more information, log on to www.mitsubishipro.com

 
01/23/2015

Data shows earth's surface temperature increase to a new high

01/22/2015

New reports show ownership could have fast benefits.

01/21/2015

New formula kills germs, prevents them from reappearing.

01/20/2015

 Study shows properly maintained roofing can last as long as buildings.

01/19/2015

Increases projected at nearly 10% per year.

01/16/2015

Pollution, health improvements more powerful motivators than cost savings.

01/15/2015

Administration looks to cut GHGs from oil, natural gas production.

01/14/2015

Vegetation effective at dampening noise.

01/13/2015

Database will aid in making green purchasing decisions. 

01/12/2015

Includes best practices for energy monitoring and reduction.

01/09/2015

Study shows majority of reserves must be left alone to mitigate climate change.

01/08/2015

Energy department looks to standardize definition.

01/07/2015

Plus 12 best practices to reduce operating costs. 

01/06/2015

Improvements extend beyond energy efficiency to carbon emissions.

01/05/2015

Rule expected to cut carbon emissions, electricity use in lighting.

01/02/2015

Data storage pattern for media improves light absorption. 

12/31/2014

Partnerships will help communities prepare for electrical disruptions.

12/30/2014

Scientists find chemical attractants that trap the insects.

12/29/2014

Older buildings will improve resiliency to earthquakes.

12/24/2014

New DD Green program looks to improve restaurant sustainability.

Page 1 of 49
FirstPrevious[1]2345678910NextLast

Upcoming Webinars

Sponsored Links