1652315947409 Economizer Must Dos

6 Economizer Must-Dos

June 6, 2013
A maintenance checklist for air-side units.

How often do you inspect your economizer?

It can be easy to put this equipment on the deferred maintenance list because it’s not always obvious if something is malfunctioning. But simply inspecting and testing the unit once or twice a year can save money and energy.

Check these six potential trouble spots to make sure your economizer is still working as hard as it can for your facility.

1) Check the Dampers
The dampers are a common source of economizer problems and can sometimes get stuck, leading the rest of your HVAC system to consume more energy trying to compensate. Your economizer maintenance should absolutely include a comprehensive visual inspection of all things damper-related to make sure the components are in working order.

“Maintenance on the dampers would consist of checking the operation of the actuator, which opens and closes the damper. Check the dampers’ adjustments to make sure they fully open and close,” recommends Wayne Drooks, senior associate and mechanical group leader for Integrated Design Group. “Also check for broken linkages between the actuators and the damper blades themselves – sometimes they fail. The blades can get jammed, either through debris that’s been pulled in or corrosion in certain environments.”

The seals at the ends of the blades should also be checked regularly because they wear out over time, Drooks adds.

“If you put off maintenance and the dampers don’t operate properly, you’ll lose the efficiency on your economizer and won’t realize the savings you should have,” Drooks says. “You’re basically throwing money out of the window.”

2) Calibrate Sensors
Your economizer’s sensors determine when the dampers should open or close and by how much, so it’s important to make sure they’re functioning correctly. A two-way radio and a coworker are needed to test the sensors, explains Dave Moser, senior engineer for PECI.

“One person is actually at the sensor with a handheld instrument to measure the value at the sensor, and the other person reads the value at the control system at the same time. If there’s a big difference, the sensor might need to be either calibrated or replaced,” Moser explains. “Some facilities can tolerate larger differences in the values, but mission critical and high-tech facilities have tighter tolerances for their sensors.”

Also pay attention to the physical location of the sensors, Drooks recommends. This can affect their accuracy.

“Not only do they need to be recalibrated, but proper location of the sensors is important,” Drooks says. “Sometimes they’re just not put in the right place or the outside air temperature sensor might be in the sun, a shaded location, or an exhaust outlet from the building where it wouldn’t read the right temperature.”

3) Test Controls and Sequences
Next, ensure that the control sequence is working properly and adjust the setpoints to achieve the most efficient operation. It helps to have a second person help out with this task as well, Drooks explains.

“If the control system is commanding the dampers to open or close, your system at the workstation may be telling you they’re open or closed, but you don’t actually know until someone goes and watches it,” Drooks explains. “Also, look at what’s going on in your building when you adjust the operating setpoints. Can you raise that return air temperature a little bit and get more hours of cooling?”

Why Economizers Fail and Increase Energy Use

  • Jammed or frozen outdoor air damper
  • Broken or disconnected linkage
  • Nonfunctioning actuator or disconnected wire
  • Malfunctioning outdoor air or return air temperature sensor
  • Malfunctioning controller
  • Faulty control settings
  • Installed or wired incorrectly

This strategy is most valuable in data centers, Drooks says. The type of space served by the economizer will tell you how far you can expand the allowable temperature range.

“In an office space, the return air would be around 80 degrees F. because you’re trying to keep the space at 70,” Drooks explains. “In a computer room or data center, you could have the return air temperature run up to 90 to 95 degrees F., where it’s at least giving you some partial cooling. You can increase the number of hours per year that the economizer operates, and ultimately you’re saving money by expanding your acceptable conditions.”

This part of the inspection should also include a brief check to make sure no one has overridden the damper controls, Drooks adds.

“One big thing that happens in a lot of buildings is that the operators disable the outside air dampers closed because it’s cheaper to run the units on full air recirculation than outside air,” he says. “That only requires a simple inspection.”PageBreak

4) Assess Filter Performance
Are you using the right filters for your environment? Most office buildings can use filters graded between MERV 8 and MERV 13, Moser says, while cleanroom areas like laboratories and spaces with high-tech equipment would likely want higher grades.

“If you’re located in an area where the outside air smells for whatever reason, some facilities use charcoal filtration in order to scrub the smells out,” Moser adds. “There was a project we worked on in Utah where if the wind was right, you could actually smell a rendering plant. They were looking hard at charcoal filtration.”

Data centers also benefit from installing particulate sensors, either in the unit itself or on the roof, to determine exactly what pollutants could affect the sensitive equipment inside, Drooks notes.

For example, corrosive pollutants such as salty air in ocean-adjacent places wreak havoc on cords and other sensitive electronic components. Periodic emergencies can also cause emissions that can affect your economizer.

“If you have smoke from a fire down the street and it gets pulled into the building, it’s going to set off all of your smoke detectors, which in some cases are set up to shut off a lot of your equipment,” Drooks says. “That could mean a disruption of service to certain types of clients.”

5) Consider the Data
If you have the hardware to support it, collecting energy data is a great way to monitor performance. A robust building management system (BMS) makes the job especially easy and can also aid in testing, Moser says.

“There’s an advantage to observing operation at the BMS rather than having to use separate data loggers,” Moser explains. “Some of the more sophisticated building management or automation systems can program rules into the system so that smart alarms are sent to the operators if the BMS notices the economizer isn’t working properly.”

Does your BMS have trending capabilities? Compare sensor readings and the time of day the economizer is operating to look for signs the unit isn’t functioning optimally.

“Trend the outside air temperature and humidity, when the economizer is in operation, and what the return air and mixed air conditions are,” Drooks recommends. “You want to make sure they’re operating at the times that they should for the maximum number of hours a year that they can.”

6) Rinse and Repeat
Finished checking the outside air components? Go back and perform the same tests on the relief and return air. Many FMs are tempted to skip this part and can wind up with inefficient operation and other adverse outcomes as a result.

“Many times we see economizers overridden because the relief air system isn’t working properly,” Moser explains. “When you use 100% outside air, the building becomes too pressurized and the doors don’t close properly. That can be a security issue.”

Too much outside air can overwhelm your mechanical cooling too, leading to overheated spaces, increased comfort complaints, and higher energy costs, Moser adds.

“The thing with economizers is that there’s not a visible issue. People don’t always notice if they’re not working,” Moser explains. “The building can limp along even if the economizer’s not functioning properly. It can be invisible, and the only symptom is higher energy costs.”

Janelle Penny [email protected] is associate editor of BUILDINGS.

About the Author

Janelle Penny | Editor-in-Chief at BUILDINGS

Janelle Penny has been with BUILDINGS since 2010. She is a two-time FOLIO: Eddie award winner who aims to deliver practical, actionable content for building owners and facilities professionals.

Voice your opinion!

To join the conversation, and become an exclusive member of Buildings, create an account today!

Sponsored Recommendations